Specjalne wykonania wentylatorów HCBT EX do użytku w strefach zagrożenia wybuchem oprócz modeli HCBT/4-250, HCBT/6-355, HCBT/6-400; model HCBT/6-400 dostępny z silnikiem 230/400 V; modele dostępne do wielkości HCBT-1000. Oznaczenie: ATEX II 2G Ex e II T3, IP55, klasa izolacji F.
Charakterystyki pracy i wymiary zgodnie z danymi wentylatorów HCBT w wykonaniu standardowym.
Modele 800 i 1000 mm:
| Typ | wydajność max | ciśnienie max | moc max |
prędkość obrotowa | natężenie max | napięcie | poziom ciś. akust.* |
temp. min |
temp. max |
masa |
|---|---|---|---|---|---|---|---|---|---|---|
| m3/h | Pa | W | obr./min | A | V | db(A) | oC | oC | kg | |
| HCBT/4-315/H EXEIIT3 | 2380 | 70 | 125 | 1330 | 0.3 | 400 | 55 | -20 | 55 | 7 |
| HCBT/4-355/H EXEIIT3 | 3530 | 98 | 191 | 1380 | 0.5 | 400 | 59 | -20 | 55 | 8 |
| HCBT/4-400/H EXEIIT3 | 5020 | 115 | 283 | 1340 | 0.7 | 400 | 62 | -20 | 55 | 9 |
| HCBT/4-450/H EXEIIT3 | 6800 | 178 | 545 | 1350 | 1 | 400 | 65 | -20 | 55 | 13 |
| HCBT/4-500/H EXEIIT3 | 9140 | 170 | 810 | 1390 | 1.6 | 400 | 68 | -20 | 55 | 16 |
| HCBT/4-560/H EXEIIT3 | 12950 | 210 | 1285 | 1390 | 2.3 | 400 | 70 | -20 | 55 | 22 |
| HCBT/4-630/H EXEIIT3 | 16840 | 240 | 1735 | 1385 | 3.1 | 400 | 73 | -20 | 55 | 25 |
| HCBT/4-710/H EXEIIT3 | 22400 | 275 | 2555 | 1350 | 4.4 | 400 | 74 | -20 | 55 | 27 |
| HCBT/4-800/L-X-1.5 EXEIIT3 | 23290 | 450 | 2630 | 1410 | 4.2 | 400 | 78 | -20 | 40 | 37 |
| HCBT/4-800/H-X-3 EXEIIT3 | 33100 | 480 | 4595 | 1440 | 7.4 | 400 | 84 | -20 | 40 | 52 |
| HCBT/4-900/H-X-5.5 EXEIIT3 | 46270 | 500 | 7895 | 1455 | 13.4 | 400 | 87 | -20 | 40 | 112 |
| HCBT/4-1000/L-X-3 EXEIIT3 | 39910 | 540 | 5050 | 1415 | 8.2 | 400 | 86 | -20 | 40 | 67 |
| HCBT/4-1000/H-X-5.5 EXEIIT3 | 49200 | 580 | 9225 | 1440 | 15.1 | 400 | 93 | -20 | 40 | 95 |
| HCBT/6-450/H EXEIIT3 | 4620 | 72 | 198 | 925 | 0.5 | 400 | 54 | -20 | 55 | 13 |
| HCBT/6-500/H EXEIIT3 | 6190 | 92 | 282 | 905 | 0.6 | 400 | 57 | -20 | 55 | 16 |
| HCBT/6-560/H EXEIIT3 | 8650 | 88 | 400 | 895 | 0.8 | 400 | 59 | -20 | 55 | 22 |
| HCBT/6-630/H EXEIIT3 | 10950 | 108 | 595 | 910 | 1.3 | 400 | 62 | -20 | 55 | 25 |
| HCBT/6-710/H EXEIIT3 | 15350 | 138 | 955 | 950 | 2.7 | 400 | 65 | -20 | 55 | 27 |
| HCBT/6-800/L-X-0.55 EXEIIT3 | 17600 | 200 | 1025 | 940 | 1.9 | 400 | 73 | -20 | 40 | 31 |
| HCBT/6-800/H-X-0.75 EXEIIT3 | 20630 | 205 | 1310 | 935 | 2.4 | 400 | 75 | -20 | 40 | 36 |
| HCBT/6-1000/L-X-1.1 EXEIIT3 | 28810 | 235 | 1855 | 940 | 3.4 | 400 | 79 | -20 | 40 | 56 |
| HCBT/6-1000/H-X-1.5 EXEIIT3 | 34300 | 240 | 2800 | 940 | 4.4 | 400 | 83 | -20 | 40 | 62 |
* mierzony w odległości 1.5m od wentylatora.